XTR, Elektronika, Zasilacze i przetwornice AC-DC DC-DC noty katalogowe EDW, Noty zasilacze, Elsinco, ZASILACZE, DC, XANTREX

Poza tym na świecie jest niewiele istot groźniejszych od kobiety.

Smart choice for power
XTR Series
850 W 1U Programmable
DC Power Supplies
High Power Density with Comprehensive Interface Options
The XTR Series is the new standard for powerful, programmable DC power systems. Designed for test,
production, laboratory, OEM and quality assurance applications, the XTR provides a wealth of features
to ensure accuracy and greater efficiency. It puts clean, reliable power at your disposal and delivers
stable, variable output voltage and current for a broad range of development, test and
system requirements.
Xantrex Technology Inc.
Headquarters
8999 Nelson Way
Burnaby, British Columbia
Canada V5A 4B5
800 670 0707 Toll Free
604 420 1591 Fax
High frequency, soft switching technology in the XTR Series provides up to 850 Watts in a 1U half-rack
package. This represents the highest power density available from any manufacturer. With 12 models
at 850 Watts, there is a configuration available to meet every application.
5916 195th Street NE
Arlington, Washington
USA 98223
800 446 6180 Toll Free
360 925 5144 Fax
Product Features
850 Watt model
High power density
Comprehensive digital and analog
interface options
Scalable, multi-unit design
Five year warranty
Protection Features
Foldback mode
Foldback mode delay
Under-voltage protection (UVP)
Over-temperature protection lock (OTP)
Local lockout
External shutdown
Interlock
Mechanical Specifications
XTR 850 Watt (W × H × D): 8.4 × 1.7 × 19.0 inch (214 × 43.6 × 483 mm)
Weight: 11 lb (5kg)
Options
Ethernet and GPIB interfaces
Rack mount kits
www.xantrex.com
© 2006 Xantrex Technology Inc. All rights reserved. Xantrex is a registered trademark of Xantrex International. Printed in Canada
 Smart choice for power
XTR 850 Watt Electrical Speciications for 6 V to 600 V Models
Models
6-110 8-100 12-70 20-42 33-25 40-21 60-14 80-10.5 100-8.5 150-5.6 300-2.8 600-1.4
Output ratings
Output voltage
1
6 V
8 V
12 V 20 V 33 V 40 V 60 V 80 V 100 V 150 V 300 V 600 V
Output current
2
110 A 100 A 70 A 42 A 25 A 21 A 14 A 10.5 A 8.5 A 5.6 A 2.8 A 1.4 A
Output power
3
670 W 810 W 850 W 850 W 835 W 850 W 850 W 850 W 860 W 850 W 850 W 850 W
Line regulation
Voltage (0.005% of rated output voltage +2 mV)
4
2.3 mV 2.4 mV 2.6 mV 3.0 mV 3.7 mV 4 mV 5 mV 6 mV 7 mV 9.5 mV 17 mV 32 mV
Current (0.01% of rated output current +2 mA)
5
13 mA 12 mA 9 mA 6.2 mA 4.5 mA 4.1 mA 3.4 mA 3.1 mA 2.9 mA 2.6 mA 2.3 mA 2.1 mA
Load regulation
Voltage (0.005% of rated output voltage +2 mV)
6
2.3 mV 2.4 mV 2.6 mV 3.0 mV 3.7 mV 4 mV 5 mV 6 mV 7 mV 9.5 mV 17 mV 32 mV
Current (0.02% of rated output current +5 mA)
7
27 mA 25 mA 19 mA 13.4 mA 10 mA 9.2 mA 7.8 mA 7.1 mA 6.7 mA 6.1 mA 5.6 mA 5.3 mA
Output noise (rms, 300 kHz)
Voltage
8 mV 8 mV 8 mV 8 mV 8 mV 8 mV 8 mV 8 mV 8 mV 10 mV 25 mV 50 mV
Current
8
200 mA 180 mA 120 mA 75 mA 60 mA 45 mA 35 mA 25 mA 20 mA 16 mA 10 mA 6 mA
Output noise (p-p, 20 MHz)
Voltage
50 mV 50 mV 50 mV 50 mV 50 mV 50 mV 50 mV 80 mV 80 mV 100 mV 150 mV 250 mV
Maximum recommended remote sense
1 V
1 V
1 V
1.5 V 2 V
2 V
3 V
5 V
5 V
5 V
5 V
5 V
Line drop compensation per line
9
Up-prog. response time, 0~Vmax
10
60 ms 60 ms 60 ms 60 ms 60 ms 60 ms 60 ms 100 ms 100 ms 100 ms 150 ms 250 ms
Down-prog. response time: full load
50 ms 50 ms 50 ms 50 ms 50 ms 50 ms 50 ms 80 ms 100 ms 150 ms 150 ms 250 ms
Down-prog. response time: no load
300 ms 400 ms 500 ms 600 ms 700 ms 800 ms 900 ms 1000 ms 1200 ms 1800 ms 2200 ms 3500 ms
Over-voltage trip point
0.5–7.5 V 0.5–10 V 1–15 V 1–24 V 2–39 V 2–44 V 3–66 V 3–95 V 3–125 V 3–180 V 5–330 V 5–660 V
Eficiency
11
75/77% 77/80% 81/84% 82/85% 83/86% 83/87% 83/87% 83/87% 83/87% 83/87% 83/87% 83/87%
1. Minimum output voltage is guaranteed to be 0.2% of the rated voltage at zero output setting.
2. Minimum output current is guaranteed to be 0.4% of the rated current at zero output setting when measured with rated load resistance.
3. Total output power is also based on AUX1 Output Voltage (5 V) and AUX1 Output Current (0.5 A) and AUX2 Output Voltage (15 V) and AUX2 Output Current (0.5 A).
4. From 85–132 Vac or 170–265 Vac, constant load.
5. From 85–132 Vac or 170–265 Vac, constant load.
6. From no load to full load, constant input voltage.
7. For load voltage change, equal to the unit voltage rating, constant input voltage.
8. For 6 V models the ripple is measured at 2–6 V output voltage and full output current. For other models, the ripple is measured at 10–100% output voltage and full output current.
9. When using remote sense, the total of the load voltage and the load line drops must not exceed the rated output of the power supply. For example, for an XTR 6-110 in an application with 1 V of load line loss
(0.5 V/Line), the maximum available load voltage would be 6–1= 5 V. Note: The unit may operate at higher output voltages than this, but there is no guarantee that the power supply will meet performance
speciications. Ultimately, the upper limit of the output voltage will be determined by internal circuitry of the power supply (non-adjustable).
10. With rated, resistive load.
11. At 100/200 Vac input voltage and maximum output power.
Applies to all footnotes:
Programming and readback: RS-232, RS-485, USB built in. GPIB, Ethernet optional.
Speciications are guaranteed from 1% to 100% of the rated output voltage, current, and power.
© 2006 Xantrex Technology Inc. All rights reserved. Xantrex is a registered trademark of Xantrex International. Printed in Canada
 
  • zanotowane.pl
  • doc.pisz.pl
  • pdf.pisz.pl
  • kachorra.htw.pl